adamczewski elektronische messtechnik-EX-COMPONENTS 防爆零部件 模擬標準信號 接觸放大器

模擬標準信號

AD-STVEX 710 GVD

產品介紹

電源隔離放大器用于為安裝在危險區域的變送器提供本質安全電源。電源隔離放大器本身作為相關電氣設備安裝在非危險區域(即安全區域)。信號被電隔離并傳輸到非危險區域。無源輸入還允許來自危險區域的有源信號。有源電流輸出、電流吸收輸出和電壓輸出便于適應后續信號輸入。該設備可在 24 V DC 或 230 V AC 下運行。

產品參數

Transmitter input, intrinsically safe
Feeding voltage23V @ 4mA … 16V @ 20mA
Maximum measuring range0 … 22 mA
Maximum short circuit current68 mA
Current input, intrinsically safe
Maximum measuring range0 … 22 mA
Input resistance50 Ohm
Current output, active
Maximum output range0 … 22 mA
Max. burden500 Ohm
Current sink output, passive
Maximum output range0 … 22 mA
Max. external supply voltage25 V DC
Max. burden(Uextern?– 2V) / 20mA
Output voltage
Maximum output range0 … 11 V
Min. burden2 kOhm
Transmission behaviour
Resolution input~ 20 μA/LSB
Resolution current output~ 20 μA/LSB
Resolution voltage output~ 10 mV/LSB
Maximum error0,2 % of full scale
Temperature influence~ 50 ppm/K
Response time~ 100 ms (10 … 90 %)
Auxiliary voltage
Range20 … 120 V DC / 50 … 250 V AC
Power consumption1,8 W / 3,5 VA
Environmental conditions
Ambient temperature-20 … +60 °C
Approval
ATEXII (1) G [Ex ia Ga] IIC
II (1) D [Ex ia Da] IIIC
Type examination certificateBVS 11 ATEX E 013 X
StandardsEN 60079-0, EN 60079-11
EN 60079-26, EN 61241-11
EMC
Product family standardEN 61326-1
Emitted interferenceEN 55011, CISPR11 Kl. B, Gr. 1
Electrical safety requirements
Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2

 

接觸放大器

AD-KVEX 100/200 GVD

產品介紹

接觸放大器(開關放大器)優選地用于保護弱傳感器接觸或放大二進制傳感器信號。 AD-KVEX 100/200 GVD 提供在觸點輸出處放大的邏輯輸入信號。典型的輸入信號是簧片觸點、符合 Namur Namur (DIN EN 60947-5-6) 的信號傳感器或電阻變化。在輸出端,提供重載和無源觸點。對于每個導管,邏輯切換方向以及線路故障識別是可單獨切換的。 AD-KVEX 100/200 GVDO 版本具有無磨損半導體輸出,也通過光學隔離進行電流隔離。該器件包含電子寬范圍電源,可以在寬電源電壓范圍內運行。

產品參數

Signal input
Min. pulse width100 ms
Namur supply voltageCa. 8,2 V DC +/-3%
Logic level, Low< 1,6 mA
Logic level, High> 1,9 mA
Wire breakage detection< 0,2 mA
Short circuit detection> 7,8 mA
Signal typesInitiator DIN EN 60947-5-6, contact, transistor
Contact output
Maximum switching load AC250 V, 2 A
Maximum switching load DC50 V, 2 A
Contact constructionPotential-free changeover
Switching operations mechanical1 x 10?7
At 230V/2A AC, cos(phi)=16 x 10?5
At 230V/2A AC, cos(phi)=0,42 x 10?5
At 50V/2 A DC2 x 10?5
Semiconductor output
Max switching voltage30 V DC
Max. switching current50 mA DC
Supply
Voltage range AC50 … 250 V AC, 50/60 Hz
Nominal voltage AC230 V AC
Power consumption AC3,5 VA (2,3 VA ; KVEX 100 GVD)
Voltage range DC20 … 120 V DC
Nominal voltage DC24 V DC
Power consumption DC1,8 W (1W ; KVEX 100 GVD)
Transmission behaviour
Response time~ 100 ms
Housing
Dimensions (WxHxD)23 x 110 x 134 mm
Type of protectionIP 20
Connection methodDetachable terminal clamp
Terminals, wire cross section2,5 mm2 flex wire / 4 mm2 one wire
Bolting torque terminals0,5 Nm
Weight~ 115 g
Manner of fastening35 mm DIN rail 35mm (EN50022)
Environmental conditions
Ambient temperature-20 … +60 °C
Storage and transport-20 … +70 °C (no condensation)
Approval
ATEXII(1) G [Ex ia Ga] IIC
II(1) D [Ex ia Da] IIIC
EU-Type Examination CertificateBVS 16 ATEX E 038 X
Safety Specifications per channel
Voltage Uo9,56 V DC
Current Io10,62 mA DC
Power Po25,4 mW
Max. external capacitance Co
||C
||B |||C
||A
3,6 μF
26 μF
210 μF
Max. external inductance Lo
||C
||B |||C
||A
315 mH
1261 mH
2522 mH
Max. external inductance / resistance ratio Lo/Ro
||C
||B |||C
||A
1,41 mH/Ohm
5,65 mH/Ohm
11,3 mH/Ohm
Internal capacitance CiN/A
Internal inductance LiN/A
Safety Specifications 2 channels parallel
Voltage Uo9,56 V DC
Current Io21,24 mA DC
Power Po50,8 mW
Max. external capacitance Co
||C
||B |||C
||A
3,6 μF
26 μF
210 μF
Max. external inductance Lo
||C
||B |||C
||A
78,8 mH
315,25 mH
630,5 mH
Max. external inductance / resistance ratio Lo/Ro
||C
||B |||C
||A
0,706 mH/Ohm
2,826 mH/Ohm
5,565 mH/Ohm
Internal capacitance CiN/A
Internal inductance LiN/A
EMC
Product family standardEN 61326-1?1)
Emitted interferenceEN 55011, CISPR11 Cl. B, Gr. 1
Electrical safety requirements
Product family standardEN 61010-1
Overvoltage categoryII
Pollution degree2
Galvanic isolation, test voltages
Input / output3 kV, 50 Hz (1 min.)
Signal / supply unit3 kV, 50 Hz (1 min.)
Protection circuits
InputElectrical surge protection
Power supplyProtection against over voltage, over temperature and reverse polarity