2113 SDS2 Trip Computer CPU Power Supply 電源

Tyne’s replacement power supply for the SDS2 Trip Computer CPU was designed to satisfy the demanding Nuclear Technical Specification of the original power supply that has been in service for 30 years. The new model has a completely redesigned circuit board using high quality, modern electronic components.

Tyne的更換電源為 SDS2 跳閘計(jì)算機(jī) CPU 的設(shè)計(jì), 以滿足苛刻的核技術(shù)規(guī)格的原始電源已在服役了30年。新的模型有一個(gè)完全重新設(shè)計(jì)的電路板使用高品質(zhì), 現(xiàn)代電子元件。

Nuclear power plant owners have expressed recent concerns regarding the quality of replacement power supplies from some vendors because of use of commercial components of sub-standard quality. To address this issue, Tyne designed its power supply from scratch, using custom-wound transformers, and all components positioned for easy inspection by Tyne and its customers.核電廠業(yè)主最近對(duì)一些供應(yīng)商更換電源的質(zhì)量表示關(guān)注, 因?yàn)槭褂昧朔謽?biāo)準(zhǔn)質(zhì)量的商業(yè)部件。為解決這一問題, Tyne從零開始設(shè)計(jì)其電源, 使用自定義纏繞變壓器, 以及所有組件的位置, 以方便地檢查, 由 Tyne和其客戶。

Specifications

Input 115 VAC
Outputs
  • +5 Vdc output at 20 amps.- Ripple & noise = 25mV(p-p)
  • +12 Vdc output at 12 amps – Ripple & noise = 25mV(p-p)
  • +15 Vdc output at 0.50 amps – Ripple & noise = 0.8 mV(p-p)
  • –15 Vdc output at 0.50 amps -Ripple & noise = 0.8 mV(p-p)
  • Each side of the centre tapped 31.6-volt AC output transformer (15.8 volts to centre tap of transformer)
Efficiency 80% overall
Stability Semi-regulated output for bus stability
MTBF 40 years
Qualification Testing
  • Seismic
  • Aged for equivalent of 30 years
  • Thermal performance 10oC to 50oC , ambient condition -18°C to +60°C
  • Relative humidity 95% RH
  • MIL STD 461E for Electromagnetic Interference Emissions and Susceptibility Conducted Susceptibility, 30 Hz to 150 KHz, Power Lead. Method CS101
  • Conducted Susceptibility, bulk cable injection, 10 kHz to 200 MHz CS114
  • Conducted Susceptibility, bulk cable injection, Impulse excitation: CS115
  • Conducted Susceptibility, damped sinusoidal transients, cables and power leads 10 kHz to 100 MHz. CS 116
  • Radiated Susceptibility, Magnetic Fields 30 Hz to 100 kHz RS101
  • Radiated Susceptibility, electric field, 2 MHz to 500 MHz RS103
  • Conducted Emission Power Leads CE102: 10 KHz to 10 MHz.
  • Radiated Emissions, RE 102 Electric Field 10 kHz to 18 GHz (test to 500 MHz only).
Parallel operation supported
Cooling No fan required for cooling
Circuit Protection Over–current, over–voltage, reverse voltage and over–temp protection
Line regulation < 0.4% over the variation range
Load Regulation < 0.4% from no load to full load
Over voltage protection 125% of the output DC voltages
ResponseTime 1μs to 1% after a 25% load change at 5A/μs
Hold-up time 20 msec
Fold back current limit with automatic recovery after overload is removed.
Quality Assurance NQA-1, CSA-Z299.1, CSA-N286.2